Led Status Displays - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Configuring the network
Modbus RTU

LED status displays

Variable mapping
Via
0x232B:001 ... 0x232B:024 (P530.01 ...
of the inverter.
Format: 0xiiiiss00 (iiii = index hexadecimal, ss = subindex hexadecimal)
The display of the internal Modbus register numbers in
(P531.01 ... 24)
is generated automatically. Since 32-bit parameters require two registers,
there is no 1:1 assignment.
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum
determined is displayed in
use it for comparison in the Modbus master. In this way it can be checked whether the
inverter currently queried is configured correctly for the respective application.
Parameter
Name / value range / [default setting]
0x232B:001 ...
Modbus parameter mapping: Parameter 1 ... Parame-
0x232B:024
ter 24
(P530.01 ... 24)
(Para. mapping: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
0x232C:001 ...
Modbus register assignment: Register 1 ... Register 24
0x232C:024
(Reg. assigned: Register 1 ... Register 24)
(P531.01 ... 24)
• Read only
0x232D
Modbus verification code
(P532.00)
(Verificationcode)
• Read only
9.5.9
LED status displays
Information about the Modbus status can be obtained quickly via the "MOD-RUN" and "MOD-
ERR" LED displays on the front of the inverter.
The meaning can be seen from the tables below.
Inverter not active on the Modbus bus (yet)
LED "MOD-RUN"
LED "MOD-ERR"
off
Both LEDs are flickering alternately
Inverter active on the Modbus
The green "MOD-RUN" LED indicates the communication status:
LED "MOD-RUN"
off
on
The red "MOD-ERR" LED indicates an error:
LED "MOD-ERR"
off
Blinking
290
24), 24 registers can be mapped to parameters
0x232D
(P532.00). The user can read this "validation code" and
Meaning
Internal error
on
Automatic detection of baud rate and data format active.
Communication status
No reception / no transmission
Reception / transmission active
Error
No fault
Communication error
0x232C:001 ... 0x232C:024
Info
Mapping entries for Modbus register 40103 ... 40149.
• Format: 0xiiiiss00 (iiii = index, ss = subindex)
Display of the internal Modbus register number starting from which the
parameter mapped in
0x232B:001 ... 0x232B:024 (P530.01 ... 24)
stored.
• For the first parameter mapped, always 2500.
• From the second parameter mapped, 2500 + offset. The offset results
from the data types of the previously mapped parameters.
is