14.16.1.1 Example 1: Output voltage 0 ... 10 V ≡ output frequency 0 ... 100 Hz
In this configuration, a voltage is provided at the analog output proportionately to the current
output frequency of the inverter (1 V ≡ 10 Hz, resolution 0.1 Hz).
Parameter
0x2639:001 (P440.01)
0x2639:002 (P440.02)
0x2639:003 (P440.03)
0x2639:004 (P440.04)
Output frequency [1]
14.16.1.2 Example 2: Output voltage 2 ... 10 V ≡ output frequency 30 ... 60 Hz
In this configuration, the output range 2 ... 10 V is used for the output of the output frequency
(resolution: 0.1 Hz). The example shows how the signals outside the signal range (here:
30 ... 60 Hz) are cut off.
Parameter
0x2639:001 (P440.01)
0x2639:002 (P440.02)
0x2639:003 (P440.03)
0x2639:004 (P440.04)
Output frequency [1]
Name
Analog output 1: Output range
Analog output 1: Function
Analog output 1: Min. signal
Analog output 1: Max. signal
0x2639:002
[V]
10
1
0
0
Name
Analog output 1: Output range
Analog output 1: Function
Analog output 1: Min. signal
Analog output 1: Max. signal
0x2639:002
[V]
10
2
0
0
Flexible I/O configuration
Setting for this example
0 ... 10 VDC [1]
Output frequency [1]
0
1000
Max
V
Min
100
10.0
Setting for this example
2 ... 10 VDC [3]
Output frequency [1]
300
600
Max
V
Min
300
600
30.0
60.0
Configuration of analog outputs
Analog output 1
X3
AO1
1000
[0.1 Hz]
100.0 [Hz]
X3
AO1
[0.1 Hz]
[Hz]