Baud Rate Setting; Monitoring - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Configuring the network
PROFIBUS

Baud rate setting

9.6.4
Baud rate setting
At the class 1 DP master, the desired baud rate is set. All masters at the bus must be set to the
same baud rate.
The parameters for the baud rate of the device are described below.
Details
The inverter detects the baud rate automatically.
The active baud rate is displayed in
The status of automatic detection is displayed in
Parameter
Name / value range / [default setting]
0x2342:002
Active PROFIBUS settings: Active baud rate
(P511.02)
(PROFIBUS diag.: Active baud rate)
• Read only
0 12 Mbps
1 6 Mbps
2 3 Mbps
3 1.5 Mbps
4 500 kbps
5 187.5 kbps
6 93.75 kbps
7 45.45 kbps
8 19.2 kbps
9 9.6 kbps
15 Search
0x2348:002
PROFIBUS Status: Watchdog status
(P516.02)
(PROFIBUS Status: Watchdog status)
• Read only
0 BAUD_SEARCH
1 BAUD_CONTROL
2 DP_CONTROL
9.6.5

Monitoring

The inverter can give a parameterisable response to various PROFIBUS errors.
The parameters for setting network monitoring functions are described below.
Details
The following table lists the PROFIBUS errors that can be set for a response.
Event
Communication to the PROFIBUS master is continuously interrupted.
Data exchange via PROFIBUS has been terminated.
The inverter has received invalid configuration data from the master.
An error has occurred during the initialisation of the PROFIBUS interface.
The process data received are invalid.
Parameter
Name / value range / [default setting]
0x2342:003
Active PROFIBUS settings: Watchdog time
(P511.03)
(PROFIBUS diag.: Watchdog time)
• Read only
296
0x2342:002
(P511.02).
0x2348:002
(P516.02).
Info
Display of the active baud rate.
Automatic baud rate detection active.
Display of the current state of the watchdog state machine (WD-STATE).
The inverter (slave) is able to detect the baud rate automatically.
After detecting the correct baud rate, the inverter (slave) status changes
to BAUD_CONTROL, and the baud rate is monitored.
The DP_CONTROL state serves to the response monitoring of the master.
Display in
0x2349
0x2349
0x2349
0x2349
0x2349
Info
Display of the watchdog monitoring time specified by the master.
• Monitoring starts with the arrival of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactiva-
ted.
• A change in the watchdog monitoring time in the master is effective
immediately.
Response can be set in Default setting
(P517.00), Bit 0
0x2859:001 (P515.01)
(P517.00), Bit 1
0x2859:002 (P515.02)
(P517.00), Bit 2
0x2859:003 (P515.03)
(P517.00), Bit 3
0x2859:004 (P515.04)
(P517.00), Bit 4
0x2859:005 (P515.05)
Error
No response
Error
Error
Trouble