9.5.10

Restart communication

The following parameter can be used to restart communication.
Details
A restart of communication is required after changes of the interface configuration (e. g. node
address and baud rate) in order that the changed settings become effective.
For restarting communication, there are two options:
a) Switch inverter off and on again.
b) Set the selection = "Restart with current values [1]" in
Parameter
Name / value range / [default setting]
0x2320
Modbus communication
(P508.00)
(Modbus comm.)
0 No action/no error
1 Restart with current values
9.5.11

Response time setting

Define a minimum time delay between the reception of a valid Modbus message and the
response of the inverter.
Especially at higher baud rates, defining a minimum time delay ensures the data exchange
between transmitter (Modbus master) and receiver (e. g. inverter).
Parameter
Name / value range / [default setting]
0x2321:004
Modbus settings: Minimum response time
(P510.04)
(Modbus sett.: Min. resp. time)
0 ... [0] ... 1000 ms
Configuring the network
0x2320
(P508.00).
Info
1 = restart communication in order that changed settings of the interface
configuration become effective.
Info
Modbus RTU
Response time setting
291