Basic setting

Mains voltage

7.1
Mains voltage
The rated mains voltage set for the inverter has an impact on the operating range of the inver-
ter.
Details
By default, the rated mains voltage in
code of the inverter.
Check the setting of the rated mains voltage in
that it matches the actual mains voltage applied!
Region
Inverter
EU
i500, 230 V, 1-phase
US
i500, 230 V, 1-phase
EU
i500, 230 V, 1/3-phase
US
i500, 230 V, 1/3-phase
EU
i500, 400 V, 3-phase
US
i500, 480 V, 3-phase
EU
i500, 120 V, 1-phase
US
i500, 120 V, 1-phase
Notes regarding the table:
The inverter types 400/480 V can be used with different mains voltages. For setting the
internal limit values, the rated mains voltage can be set in
user.
The inverter types 120 V are designed for a 1-phase 120-V mains voltage and 3-phase 230-
V three-phase AC motors. These inverters have an internal DC bus similar to the 230-V
inverters. The voltage thresholds correspond to the ones of the 230-V inverters.
If the inverter is reset to the delivery status, the rated mains voltage is also reset to the
default setting listed in the table according to the product code.
The following results from the rated mains voltage set:
the error threshold for monitoring the DC-bus voltage and
the voltage threshold for braking operation ("brake chopper threshold").
Monitoring of the DC-bus voltage
The warning thresholds for monitoring are adjustable.
The error thresholds and reset thresholds for monitoring result from the rated mains volt-
age set:
Rated mains volt-
age
Warning threshold
Setting in
Setting in
0x2540:001
0x2540:002
(P208.01)
(P208.02)
If the DC-bus voltage of the inverter falls below the undervoltage error threshold, the
"Trouble" response is triggered.
Without external 24-V supply: Motor behaves according to
With external 24-V supply: At undervoltage, motor behaves according to disturbance
response.
If the DC-bus voltage of the inverter exceeds the overvoltage error threshold, the "Fault"
response is triggered.
The motor does not restart automatically after the overvoltage monitoring func-
tion has been activated.
144
0x2540:001 (P208.01)
Product code
0x2000:001 (P190.01)
i5xAExxxBxxxx0xxxx
i5xAExxxBxxxx1xxxx
i5xAExxxDxxxx0xxxx
i5xAExxxDxxxx1xxxx
i5xAExxxFxxxx0xxxx
i5xAExxxFxxxx1xxxx
i5xAExxxAxxxx0xxxx
i5xAExxxAxxxx1xxxx
Undervoltage thresholds
Error threshold
Reset threshold
Display in
Display in
0x2540:003
0x2540:004
(P208.03)
(P208.04)
is set according to the product
0x2540:001
(P208.01). Ensure
Rated mains voltage
Default setting
230 Veff [0]
230 Veff [0]
230 Veff [0]
230 Veff [0]
400 Veff [1]
480 Veff [2]
120 Veff [3]
120 Veff [3]
0x2540:001 (P208.01)
by the
Overvoltage thresholds
Warning threshold
Error threshold
Setting in
0x2540:005
(P208.05)
0x2838:002
(P203.02).
Possible settings
230 Veff [0]
230 Veff [0]
230 Veff [0]
230 Veff [0]
400 Veff [1], 480 Veff [2]
400 Veff [1], 480 Veff [2]
120 Veff [3]
120 Veff [3]
Reset threshold
Display in
Display in
0x2540:006
0x2540:007
(P208.06)
(P208.07)