Motor Controller Settings; Current Controller - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Motor control
Optimisation of the control loops

Motor controller settings

8.4.4
Motor controller settings
After the motor settings have been made, the different control loops must be set. For a quick
commissioning, the calculations and settings are made automatically if one of the following
optimisations is carried out:
4Motor selection from motor catalogue
4Automatic motor identification (energized)
4Automatic motor calibration (non-energized)
Details
The following controllers have an influence in the respective motor control type:
Controller

Current controller

^ 202
Field controller
^ 203
Field weakening controller
^ 203
Imax controller
^ 204
Flying restart controller
^ 205
SLVC controller
^ 205
Slip controller
^ 210
8.4.4.1
Current controller
For a quick commissioning, the calculations and settings are made automatically during the
optimisation.
For typical applications, a manual adaptation of the parameters of the current
controller is not recommended. A wrong setting may have a negative effect on
the control. For special applications, contact the manufacturer before adapting
the parameters.
Preconditions
The current controller parameters are calculated based on the stator resistance and leakage
inductance. Thus, the following parameters must be set correctly, either via optimisation or
manually (according to manufacturer-data/motor data sheet):
0x2C01:002: Stator resistance
0x2C01:003: Stator leakage inductance
4Motor equivalent circuit diagram data
Parameter
Name / value range / [default setting]
0x2942:001
Current controller parameters: Gain
(P334.01)
(Current contr.: Gain)
0.00 ... [42.55]* ... 750.00 V/A
* Default setting depending on the size.
0x2942:002
Current controller parameters: Reset time
(P334.02)
(Current contr.: Reset time)
0.01 ... [4.50]* ... 2000.00 ms
* Default setting depending on the size.
202
^ 197
^ 199
^ 200
VFC open
loop
l
l
l
VFC open loop
= V/f characteristic control
VFC closed loop
= V/f characteristic control with speed feedback
SC-ASM
= servo control for asynchronous motor
SL-PSM
= sensorless control for synchronous motor
SLVC
= sensorless vector control
^ 201
Info
Gain factor Vp of the current controller.
Reset time Ti of the current controller.
Motor control type
VFC closed
SC-ASM
SL-PSM
loop
l
l
l
l
l
l
SLVC
l
l
l
l
l
l
l