Heatsink Temperature Monitoring; Life-Diagnosis - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Parameter
Name / value range / [default setting]
0x2D40:005
Device utilisation (i*t): Error response
(P135.05)
(Device utilisat.: Error response)
2 Trouble
3 Fault
0x2DDF:001
Axis information: Rated current
• Read only: x.xx A
6.2.12

Heatsink Temperature Monitoring

Parameter
Name / value range / [default setting]
0x2D84:001
Heatsink temperature
(P117.01)
(Heatsink temp.: Heatsink temp.)
• Read only: x.x °C
0x2D84:002
Heatsink temperature: Warning threshold
50.0 ... [80.0]* ... 100.0 °C
* Default setting depending on the size.
6.2.13

Life-diagnosis

The following parameters provide some information about the use of the inverter.
This includes the following information:
Operating and power-on time of the inverter/control unit
Operating time of the internal fan
Number of switching cycles of the mains voltage
Number of switching cycles of the relay
Number of short-circuits and earth faults that have occurred
Display of the number of "Imax: Clamp responded too often" errors that have occurred.
Parameter
Name / value range / [default setting]
0x2D81:001
Life-diagnosis: Operating time
(P151.01)
(Life-diagnosis: Operating time)
• Read only: x s
0x2D81:002
Life-diagnosis: Power-on time
(P151.02)
(Life-diagnosis: Power-on time)
• Read only: x s
0x2D81:003
Life-diagnosis: Control unit operating time
(P151.03)
(Life-diagnosis: CU oper. time)
• Read only: x ns
0x2D81:004
Life-diagnosis: Main switching cycles
(P151.04)
(Life-diagnosis: Switching cycles)
• Read only
0x2D81:005
Life-diagnosis: Relay switching cycles
(P151.05)
(Life-diagnosis: Relay cycles)
• Read only
0x2D81:006
Life-diagnosis: Short-circuit counter
(P151.06)
(Life-diagnosis: Short-circ.count)
• Read only
0x2D81:007
Life-diagnosis: Earth fault counter
(P151.07)
(Life-diagnosis: Earthfault count)
• Read only
Diagnostics and fault elimination
Heatsink Temperature Monitoring
Info
Selection of the response to be executed when the device overload
monitoring function is triggered.
Associated error code:
9090
|
0x2382
- I*t error
4Error types
^ 139
Display of the rated current of the axis.
Info
Display of the current heatsink temperature.
Warning threshold for temperature monitoring.
• If the heatsink temperature exceeds the threshold set here, the inver-
ter outputs a warning.
• The warning is reset with a hysteresis of approx. 5 °C.
• If the heatsink temperature increases further and exceeds the non-
adjustable error threshold (100 °C), the inverter changes to the
"Fault" device status. The inverter is disabled and thus any further
operation is stopped.
Info
Display showing for how long the inverter has been running so far "Oper-
ation enabled" device state).
Display showing for how long the inverter has been supplied with mains
voltage so far.
Display showing for how long the control unit has been supplied with
voltage so far. This includes the external 24-V supply and voltage supply
via USB module.
• This also includes the time within which the control unit has only
been supplied with an external 24 V voltage.
Display of the number of switching cycles of the mains voltage.
Display of the number of switching cycles of the relay.
Display of the number of short circuits that have occurred.
Display of the number of earth faults that have occurred.
Diagnostics parameter
137