Parameters

3.11 Main Menu - Drive Information - Group

15
Parameter group containing adjustable frequency drive
3
3
information such as operating data, hardware configu-
ration and software versions.

3.11.1 15-0* Operating Data

15-00 Operating hours
Range:
0 h
[0 - 0x7fffffff. h] View how many hours the adjustable
*
15-01 Running Hours
Range:
0 h
[0 - 0x7fffffff.
*
h]
15-02 kWh Counter
Range:
0 kWh
[0 - 65535
*
kWh]
15-03 Power Up's
Range:
0
[0 - 2147483647 ] View the number of times the adjustable
*
15-04 Over Temp's
Range:
0
[0 - 65535 ] View the number of adjustable frequency
*
15-05 Over Volt's
Range:
0
[0 - 65535 ] View the number of adjustable frequency
*
15-06 Reset kWh Counter
Option:
[0] Do not reset
[1] Reset counter Select [1] Reset and press [OK] to reset the
3-52
VLT
Function:
frequency drive has run. The value is
saved when the adjustable frequency
drive is turned off.
Function:
View how many hours the motor has run.
Reset the counter in 15-07 Reset Running
Hours Counter. The value is saved when
the adjustable frequency drive is turned
off.
Function:
View the output power of the adjustable
frequency drive in kWh as a mean value
over one hour. Reset the counter in
15-06 Reset kWh Counter.
Function:
frequency drive has been powered up.
Function:
drive temperature faults which have occurred.
Function:
drive overvoltages which have occurred.
Function:
kWh counter to zero (see 15-02 kWh Counter).
MG18B222 - VLT
®
HVAC Basic Drive Programming Guide
NOTE!
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option:
[0] Do not reset
[1] Reset counter Select [1] Reset counter and press [OK] to reset

3.11.2 15-3* Alarm Log

Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Error codes, values and time
stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Range:
0
[0 - 255 ] View the error code and look up its meaning in
*
Range:
0
[-32,767–
*
32,767]

3.11.3 15-4* Drive Identification

Parameters containing read-only information about the
hardware and software configuration of the Adjustable
frequency drive.
15-40 FC Type
Range:
0
[0 - 0 ] View the FC type. The readout is identical to the
*
15-41 Power Section
Range:
0
[0 - 0 ] View the FC type. The readout is identical to the
*
15-42 Voltage
Range:
0
[0 - 0 ] View the FC type. The readout is identical to the
*
®
is a registered Danfoss trademark
Function:
Running Hours counter (15-01 Running Hours)
and to zero (see also 15-01 Running Hours).
Function:
the Troubleshooting chapter.
Function:
View a description of the error. This
parameter is used in combination with
alarm 38 Internal Fault.
Function:
adjustable frequency drive series power field of the
type code definition, characters 1-6.
Function:
adjustable frequency drive series power field of the
type code definition, characters 7-10.
Function:
adjustable frequency drive series power field of the
type code definition, characters 11-12.