Terminal Configuration - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

3.9 Control Circuit Wiring

◆ Terminal Configuration

Control circuit terminals should be arranged as shown in
Figure 3.31
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
wire ends. Refer to
Table 3.10
Terminal
Terminal
Block
S1-S8, SC, SP, SN, RP,
+V, -V, A1, A2, A3, AC,
M1-M6, MA, MB, MC,
TB1, TB2
MP, AM, FM, AC, S+,
TB3, TB4
S-, R+, R-, IG, HC, H1,
H2, DM+, DM-
E (G)
TB5
E (G)
82
E
E(G) HC H1 H2 DM+ DM- IG R+ R- S+ S-
D
C
A – Terminal Block (TB 2)
B – Terminal Block (TB 5)
C – Terminal Block (TB 1)
Figure 3.24 Control Circuit Terminal Arrangement
Table
for ferrule terminal types and sizes.
Table 3.9 Wire Gauges and Torque Specifications
Tightening
Screw
Torque
Size
Nm
(lb.in.)
0.5 to 0.6
0.2 to 1.0 (24 to 17)
M3
(4.4 to 5.3)
0.2 to 1.5 (24 to 16)
0.5 to 1.0
M3.5
(4.4 to 8.9)
Figure
3.24.
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
D – Terminal Block (TB 3)
E – Terminal Block (TB 4)
3.9. For simpler and more reliable wiring, use crimp ferrules on the
Bare Wire Terminal
Applicable
Recommended
wire size
wire size
2
2
mm
(AWG)
mm
(AWG)
Stranded wire:
0.75
(18)
Solid wire:
1.0 (16)
0.5 to 2
1.25
(20 to 14)
(12)
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
A
M3 M4 M6
M1 M2 M5
MA MB MC
Ferrule-Type Terminal
Applicable
Recommended
wire size
wire size
2
2
mm
(AWG)
mm
(AWG)
0.25 to 0.5
0.5
(24 to 20)
(20)
B
Wire Type
Shielded line, etc.

Advertisement

Table of Contents
loading