F2: Analog Input Card Settings (AI-A3)

No.
(Addr.
Name
Hex)
Analog Input Option
F2-01
Card Operation
(038F)
Selection
F2-02
Analog Input Option
(0368)
Card Gain
F2-03
Analog Input Option
(0369)
Card Bias
u

F3: Digital Input Card Settings (DI-A3)

No.
(Addr.
Name
Hex)
F3-01
Digital Input Option
(0390)
Card Input Selection
Digital Input Option DI-
F3-03
A3 Data Length
(03B9)
Selection
u

F4: Analog Monitor Card Settings (AO-A3)

No.
(Addr.
Name
Hex)
F4-01
Terminal V1 Monitor
(0391)
Selection
F4-02
Terminal V1 Monitor
(0392)
Gain
F4-03
Terminal V2 Monitor
(0393)
Selection
F4-04
Terminal V2 Monitor
(0394)
Gain
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
LCD Display
All Modes
AI Function Sel
0: Option card input terminals V1, V2, and V3 replace drive
0: 3ch Individual
input terminals A1, A2, and A3.
1: 3ch Addition
1: Input signals to terminals V1, V2, and V3 are added together
to create the frequency reference.
All Modes
AI Input Gain
Sets the gain for the input signal to the analog card.
All Modes
AI Input Bias
Sets the bias for the input signal to the analog card.
LCD Display
All Modes
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
DI Function Sel
3: BCD, 1 Hz units
0: BCD 1%
4: BCD, 0.1 Hz units
1: BCD 0.1%
5: BCD, 0.01 Hz units
2: BCD 0.01%
6: BCD customized setting (5-digit), 0.02 Hz units
3: BCD 1 Hz
7: Binary input
4: BCD 0.1 Hz
The unit and the setting range are determined by F3-03.
5: BCD 0.01 Hz
F3-03 = 0: 255/100% (-255 to +255)
6: BCD(5DG) 0.01 Hz
F3-03 = 1: 40961/100% (-4095 to +4095)
7: Binary
F3-03 = 2: 30000/100% (-33000 to +33000)
When the digital operator units are set to be displayed in Hz or
user-set units (o1-03 = 2 or 3), the units for F3-01 are
determined by parameter o1-03.
Data length Sel
All Modes
0: 8bit
0: 8 bit
1: 12bit
1: 12 bit
2: 16bit
2: 16 bit
LCD Display
All Modes
Sets the monitor signal for output from terminal V1. Set this
AO Ch1 Select
parameter to the last three digits of the desired Uo-oo
monitor. Some U parameters are available only in certain
control modes.
All Modes
AO Ch1 Gain
Sets the gain for voltage output via terminal V1.
All Modes
Sets the monitor signal for output from terminal V2. Set this
AO Ch2 Select
parameter to the last three digits of the desired Uo-oo
monitor. Some U parameters are available only in certain
control modes.
All Modes
AO Ch2 Gain
Sets the gain for voltage output via terminal V2.
Description
Description
Description
B.8 F: Option Settings
Values
Page
Default: 0
267
Range: 0, 1
Default: 100.0%
Min.: -999.9
268
Max.: 999.9
Default: 0.0%
Min.: -999.9
268
Max.: 999.9
Values
Page
Default: 0
268
Range: 0 to 7
Default: 2
268
Range: 0 to 2
Values
Page
Default: 102
Range: 000 to 999
269
<1>
Default: 100.0%
Min.: -999.9
269
Max.: 999.9
Default: 103
Range: 000 to 999
269
<1>
Default: 50.0%
Min.: -999.9
269
Max.: 999.9
525
B