13.4 Programmed Operation
13.4.3 Block Command Details
Decrement Counter Command
The Decrement Counter command decrements by one the counter that is used for loop con-
trol. The following table gives the data format for the Decrement Counter command.
Attribute
*
If the link number is 0, the block is the final block in the sequence.
Delay Command
The Delay command inserts a delay time before the execution of the next command block. Set
the delay time in increments of 4 ms. If you specify any value that is not a multiple of 4 ms, the
value will be rounded down to the nearest multiple of 4 ms. The following table gives the data
format for the Delay command.
Attribute
*
If the link number is 0, the block is the final block in the sequence.
Trajectory Command
The Trajectory command starts positioning. After the SERVOPACK starts positioning, the next
command block is executed. The following table gives the data format for the Trajectory com-
mand.
Attribute
*
If the link number is 0, the block is the final block in the sequence.
Trajectory and Wait Command
The Trajectory and Wait command starts positioning. The next command block is not executed
until positioning has been completed. The next command block is executed only after the posi-
tioning operation is completed. The following table gives the data format for the Trajectory and
Wait command.
Attribute
*
If the link number is 0, the block is the final block in the sequence.
13-26
Name
1
Block Command Code
2
Link Number
Name
1
Block Command Code
2
Link Number
3
Delay
Name
1
Block Command Code
2
Link Number
3
Target Position
4
Target Velocity
5
Absolute/Incremental
Name
1
Block Command Code
2
Link Number
3
Target Position
4
Target Velocity
5
Absolute/Incremental
Data Type
Description of Attribute
USINT
Code = 0x05
Number of next command block to exe-
USINT
cute*
Data Type
Description of Attribute
USINT
Code = 0x06
Number of next command block to exe-
USINT
cute*
Delay timer value
Setting range: 0x00000001 to
DINT
0x7FFFFFFF
Unit: ms
Data Type
Description of Attribute
USINT
Code = 0x07
Number of next command block to exe-
USINT
cute*
DINT
Target position (reference units)
DINT
Target speed (reference unit/s)
BOOL
Absolute (0)/Incremental (1)
Data Type
Description of Attribute
USINT
Code = 0x08
Number of next command block to exe-
USINT
cute*
DINT
Target position (reference units)
DINT
Target speed (reference unit/s)
BOOL
Absolute (0)/Incremental (1)