Diagnostics And Interrupt - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
CHxUL CHxLL Upper limit
value Lower limit value
channel x
3.20.3

Diagnostics and interrupt

Event
Error in project
engineering/parameterization
Measuring range overflow
Measuring range underflow
Limit overflow
Limit underflow
Diagnostic buffer overflow
Communication error
Process interrupt lost
Process interrupt
Name
Bytes
PRIT_OL
1
PRIT_UL
1
PRIT_US
2
PRIT_OL Limit overflow
HB300 | SM-AIO | | en | 17-05
For each channel an upper and a lower limit may be defined. Here only values of the
nominal range may be preset, otherwise you receive a parameterization error. By preset-
ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding
limit is deactivated. As soon as the measuring value is beyond the limits and the limit
value monitoring is activated, a process interrupt is initialized.
Process
interrupt
So you may react to asynchronous events, there is the possibility to activate a process
interrupt. A process interrupt interrupts the linear program sequence and jumps
depending on the master system to a corresponding Interrupt routine. Here you can react
to the process interrupt accordingly.
With CANopen the process interrupt data a transferred via an emergency telegram.
Operating with CPU, PROFIBUS and PROFINET the process interrupt data were trans-
ferred via diagnostics telegram.
SX - Subindex for access via EtherCAT with Index 5000h
More can be found in the according manual of your bus coupler.
Function
Limit overflow channel x
Limit underflow channel x
µs ticker
Byte
Bit 7 ... 0
0
n
Bit 0: Limit overflow channel 0
n
Bit 1: Limit overflow channel 1
n
Bit 2: Limit overflow channel 2
n
Bit 3: Limit overflow channel 3
n
Bit 7 ... 4: reserved
031-1CD30 - AI 4x16Bit 0...10V > Diagnostics and interrupt
Diagnostics
interrupt
-
-
-
X
X
-
-
-
Analog Input
parameterizable
X
X
X
-
-
X
X
X
Default
SX
00h
02h
00h
03h
00h
04h ... 05h
-
-
-
X
X
-
-
-
231

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio

Table of Contents