Technical Data - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1CD45 - AI 4x16Bit 0(4)...20mA > Technical data
Output area
3.23.1

Technical data

Order no.
Type
Module ID
Current consumption/power loss
Current consumption from backplane bus
Power loss
Technical data analog inputs
Number of inputs
Cable length, shielded
Rated load voltage
Current consumption from load voltage L+ (without load)
Voltage inputs
Min. input resistance (voltage range)
Input voltage ranges
Operational limit of voltage ranges
Operational limit of voltage ranges with SFU
Basic error limit voltage ranges
Basic error limit voltage ranges with SFU
Destruction limit voltage
Current inputs
Max. input resistance (current range)
Input current ranges
Operational limit of current ranges
Operational limit of current ranges with SFU
Basic error limit current ranges
Radical error limit current ranges with SFU
Destruction limit current inputs (voltage)
Destruction limit current inputs (electrical current)
258
Addr.
Name
Bytes
+4
AI 2
2
+6
AI 3
2
No byte of the output area is used by the module.
Function
Analog value channel 2
Analog value channel 3
031-1CD45
SM 031
0414 15C4
65 mA
0.8 W
4
200 m
DC 24 V
20 mA
-
-
-
-
-
-
-
-
ü
60 Ω
0 mA ... +20 mA
+4 mA ... +20 mA
+/-0.2%
-
+/-0.1%
-
max. 24V
max. 40mA
VIPA System SLIO
IX
SX
6401h/s+2
03h
6401h/s+3
04h
HB300 | SM-AIO | | en | 17-05