Output area
DMS_CMD
Addr.
Name
+0
DMS_CMD
HB300 | SM-AIO | | en | 17-05
n
Tara
When setting or clearing the tare value, this bit is set.
As long as the corresponding command bit is set, this bit remains set.
n
Adjustment
When you save or delete the adjustment data, this bit is set.
As long as the corresponding command bit is set, this bit remains set.
n
Zero balance respectively reference point
When setting the zero balance respectively reference point this bit is set.
As long as the corresponding command bit is set, this bit remains set.
Addr.
Name
+0
DMS_CMD
Bytes
Function
1
n
Command byte Each set bit in DMS_CMD is acknowledged by a bit in
DMS_STAT.
Bit 0: Activate Input Freeze à DMS_STAT bit 0: active
Bit 1: Store adjustment à DMS_STAT bit 5: active
Bit 2: Delete adjustment à DMS_STAT bit 5: active
Bit 3: Set Tara à DMS_STAT bit 3: active
Bit 4: Delete Tara à DMS_STAT bit 3: active
Bit 5: reserved
Bit 6: Set zero point à DMS_STAT bit 7: active
Bit 7: Set reference point à DMS_STAT bit 7: active
n
Input Freeze
In the activated state no measurement values are passed to the digital filter.
By a brief activation of Input Freeze pulses, e.g. caused by a filling procedure can
be prevented, which would override the filter unnecessarily.
The status of Input Freeze can be determined at any time via bit 0 of DMS_STAT.
n
Adjustment
Store adjustment: Used to store the adjustment data when loaded with the refer-
ence weight.
Delete adjustment: Used to delete the adjustment data.
With both commands bit 5 of DMS_STAT is set. In case of error bit 4 is set.
n
Tara
Set Tara: The current value is taken as tara.
Delete Tara: Tara is reset to 0.
With both commands bit 3 of DMS_STAT is set.
n
Zero balance respectively reference point
Both commands are used for user adjustment and on both commands bit 7 of
DMS_STAT is set.
Set zero balance: Used to set the balance to 0 when operated without load.
Set reference point: Used to adjust the balance when it is loaded with a reference
weight.
031-1CA20 - AI 1x16(24)Bit Strain gauge (DMS) > In-/Output area
Bytes
Function
1
Command byte
Analog Input
IX
SX
5670h/s
01h
177