Basics and mounting
Wiring power modules
Standard wiring
PM - Power module
24
(1) DC 24V for power section supply I/O area (max. 10A)
(2) DC 24V for electronic power supply bus coupler and I/O area
For wires with a core cross-section of 0.08mm
Pos.
Function
1
---
2
DC 24V
3
0V
4
Sys DC 24V
5
---
6
DC 24V
7
0V
8
Sys 0V
I: Input
CAUTION!
Since the power section supply is not internally protected, it is to be exter-
nally protected with a fuse, which corresponds to the maximum current.
This means max. 10A is to be protected by a 10A fuse (fast) respectively
by a line circuit breaker 10A characteristics Z!
The electronic power section supply is internally protected against higher
voltage by fuse. The fuse is within the power module. If the fuse releases,
its electronic module must be exchanged!
2
up to 1.5mm
Type
Description
---
not connected
I
DC 24V for power section supply
I
GND for power section supply
I
DC 24V for electronic section supply
---
not connected
I
DC 24V for power section supply
I
GND for power section supply
I
GND for electronic section supply