YASKAWA VIPA System SLIO Manual page 90

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1BB70 - AI 2x12Bit ±10V > Parameter data
Name
Bytes
CH0FN
1
CH1FN
1
CHxFN Function number
channel x
±10V
Meas. range
(funct. no.)
±10V
Siemens S7 format
(12h)
±10V
Siemens S5 format
(22h)
90
Function
Function number channel 0
Function number channel 1
In the following there are the measuring ranges with function number listed, which were
supported by the analog module. With FFh the corresponding channel is deactivated. The
formulas listed here allow you to transform an evaluated measuring value (digital value)
to a value assigned to the measuring range (analog value) and vice versa.
Voltage
Decimal
(U)
(D)
11.76V
32511
10V
27648
5V
13824
0V
0
-5V
-13824
-10V
-27648
-11.76V
-32512
12.5V
20480
10V
16384
5V
8192
0V
0
-5V
-8192
-10V
-16384
-12.5V
-20480
Default
DS
12h
80h
12h
81h
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
CA00h
9400h
8100h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
E000h
C000h
B000h
underrange
VIPA System SLIO
IX
SX
3100h
01h
3101h
02h
Formulas