YASKAWA VIPA System SLIO Manual page 147

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
Measuring range
(funct. no.)
4 wire: 0 ... 60W
(E0h)
4 wire: 0 ... 600W
(E1h)
4 wire: 0 ... 3000W
(E2h)
CHxFO Function option
channel x
CHxUL / CHxLL channel x
HB300 | SM-AIO | | en | 17-05
Measuring value
70.55W
0 ... 60W
---
705.5W
0 ... 600W
---
3528W
0 ... 3000W
---
Depending on the Interference frequency suppression for each channel the transducer
velocity may be set.
Code*
Velocity (in ms) / channel at Interference frequency suppression
00h*
01h*
02h*
03h
04h
05h
06h
07h
08h
*) For Code 00h, 01h and 02h the tolerances of the technical data "with interference frequency suppression" are valid.
For each channel an upper and a lower limit may be defined. Here only values of the
nominal range may be preset, otherwise you receive a parameterization error. By preset-
ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding
limit is deactivated.
As soon as the measuring value is beyond the limits and the limit value monitoring is acti-
vated, a process interrupt is initialized.
031-1BD80 - AI 4x16Bit R/RTD > Parameter data
Signal range
32511
0 ... 27648
---
32511
0 ... 27648
---
32511
0 ... 27648
---
50Hz
324.1
164.2
84.2
44.1
24.2
14.2
9.2
6.6
4.2
Analog Input
Range
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
60Hz
270.5
137.2
70.5
37.2
20.5
12.2
8.0
5.9
3.8
147

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio