YASKAWA VIPA System SLIO Manual page 283

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
DIAG_EN Diagnostics
WIBRK_EN Wire break
recognition
TEMPCNF Temperature
system
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
HB300 | SM-AIO | | en | 17-05
Byte
Bit 7 ... 0
0
n
Diagnostic interrupt
00h: disabled
40h: enabled
Here you can enable respectively disable the diagnostic interrupt.
n
Byte
Bit 7 ... 0
0
n
Bit 0: Wire break recognition channel 0 (1: on)
n
Bit 1: Wire break recognition channel 1 (1: on)
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
Bit 0, 1: Temperature system
n
00: °C
01: °F
10: K
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
n
Bit 0, 1: Interference frequency suppression
01: 60Hz
10: 50Hz
n
Bit 7 ... 2: reserved
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated.
031-1LB90 - AI 2x16Bit TC > Parameter data
Analog Input
283

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio

Table of Contents