YASKAWA VIPA System SLIO Manual page 57

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
ERR_D Diagnostic
CHTYP Channel type
NUMBIT Diagnostic bits
NUMCH Channels
CHERR Channel error
CH0ERR / CH1ERR
Channel-specific
CH2ERR ... CH7ERR
reserved
HB300 | SM-AIO | | en | 17-05
Byte
Bit 7 ... 0
0
n
Bit 2 ... 0: reserved
n
Bit 3: set at internal diagnostics buffer overflow
n
Bit 4: set at internal communication error
n
Bit 5: reserved
n
Bit 6: set at process interrupt lost
Bit 7: reserved
n
Byte
Bit 7 ... 0
0
n
Bit 6 ... 0: Channel type
70h: Digital input
71h: Analog input
72h: Digital output
73h: Analog output
74h: Analog input/-output
76h: Counter
n
Bit 7: reserved
Byte
Bit 7 ... 0
0
Number of diagnostic bits per channel (here 08h)
Byte
Bit 7 ... 0
0
Number of channels of a module (here 02h)
Byte
Bit 7 ... 0
0
n
Bit 0: set at error in channel group 0
n
Bit 1: set at error in channel group 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
Channel-specific error: Channel x:
n
Bit 0: set at project engineering/parameterization error
n
Bit 1: row value above the permissible range
n
Bit 2: row value below the acceptable range
n
Bit 3: reserved
n
Bit 4: error sensor supply voltage
n
Bit 5: set at process interrupt lost
n
Bit 6: set at measuring range underflow
n
Bit 7: set at measuring range overflow
Byte
Bit 7 ... 0
0
reserved
031-1BB10 - AI 2x12Bit 0(4)...20mA - ISO > Diagnostics and interrupt
Analog Input
57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio

Table of Contents