Analog Input
031-1CD30 - AI 4x16Bit 0...10V > Parameter data
DIAG_EN Diagnostic inter-
rupt
LIMIT_EN Limit value
monitoring
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
0 ... 10V
Meas. range
(funct. no.)
0 ... 10V
Siemens S7 format
(10h)
0 ... 10V
Siemens S5 format
(20h)
230
Byte
Bit 7 ... 0
0
n
Diagnostic interrupt
Here you can enable respectively disable the diagnostic interrupt.
n
Byte
Bit 7 ... 0
0
n
Bit 0: Limit value monitoring channel 0 (1: on)
n
Bit 1: Limit value monitoring channel 1 (1: on)
n
Bit 2: Limit value monitoring channel 2 (1: on)
Bit 3: Limit value monitoring channel 3 (1: on)
n
Bit 7 ... 4: reserved
n
Byte
Bit 7 ... 0
0
n
Bit 1, 0: Interference frequency suppression channel 0
n
Bit 3, 2: Interference frequency suppression channel 1
n
Bit 5, 4: Interference frequency suppression channel 2
n
Bit 7, 6: Interference frequency suppression channel 3
e.g.: 10101010: all channels frequency suppression 50Hz
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
Voltage
Decimal
(U)
(D)
11.76V
32511
10V
27648
5V
13824
0V
0
-1.76V
-4864
12.5V
20480
10V
16384
5V
8192
0V
0
-2V
-3277
00h: disabled
40h: enabled
00: deactivated
01: 60Hz
10: 50Hz
Hex
7EFFh
6C00h
3600h
0000h
ED00h
5000h
4000h
2000h
0000h
F333h
Range
Formulas
overrange
nominal range
underrange
overrange
nominal range
underrange
HB300 | SM-AIO | | en | 17-05