YASKAWA VIPA System SLIO Manual page 134

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1BD70 - AI 4x12Bit ±10V > Diagnostic data
Name
Bytes
CH0ERR
1
CH1ERR
1
CH2ERR
1
CH3ERR
1
CH4ERR...CH
4
7ERR
DIAG_US
4
ERR_A Diagnostic
MODTYP Module informa-
tion
ERR_D Diagnostic
CHTYP Channel type
NUMBIT Diagnostic bits
134
Function
Channel-specific error channel 0
Channel-specific error channel 1
Channel-specific error channel 2
Channel-specific error channel 3
reserved
µs ticker
Byte
Bit 7 ... 0
0
n
Bit 0: set at module failure
n
Bit 1: set at internal error
Bit 2: set at external error
n
n
Bit 3: set at channel error
n
Bit 4: set at external auxiliary supply missing
n
Bit 6 ... 5: reserved
n
Bit 7: set at error in parameterization
Byte
Bit 7 ... 0
0
n
Bit 3 ... 0: module class
0101b analog module
n
Bit 4: set at channel information present
n
Bit 7 ... 5: reserved
Byte
Bit 7 ... 0
0
n
Bit 2 ... 0: reserved
Bit 3: set at internal diagnostics buffer overflow
n
n
Bit 4: set at internal communication error
n
Bit 7 ... 5: reserved
Byte
Bit 7 ... 0
0
n
Bit 6 ... 0: Channel type
70h: Digital input
71h: Analog input
72h: Digital output
73h: Analog output
74h: Analog input/-output
76h: Counter
n
Bit 7: reserved
Byte
Bit 7 ... 0
0
Number of diagnostic bits per channel (here 08h)
Default
DS
00h
00h
00h
00h
00h
00h
VIPA System SLIO
IX
SX
0Ah
0Bh
0Ch
0Dh
0Eh ... 11h
13h
HB300 | SM-AIO | | en | 17-05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio

Table of Contents