YASKAWA VIPA System SLIO Manual page 324

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Process data communication
Example 'Set Frame'
Request
Byte
Value
B0
0x30
B1
0x01
B2
0x03
B3
0x00
D00
0x03
D01
0x0D
D02
0x0C
D03
-
...
D11
Response
Byte
Value
B0
0x30
B1
0x01
B2
0x03
B3
0x00
D00
0x03
D01
0x0D
D02
0x0C
D03
-
...
D11
324
Here a Frame with FR-ID 0x01 is defined. The Frame contains the following measurands:
n
ID: 03: Counter: Active energy L1 (consumer)
ID: 13: total cos j
n
n
ID: 12: Frequency
Description
Telegram type 'Set Frame'
Ä 'FR-ID' on page 310 of the Frame to be read (FR-ID = 1)
Length user data: 3 byte
Common status (not relevant)
User data with the ID of the measurands
Remaining user data are not relevant
Description
Telegram type 'Set Frame' from the request
FR-ID of the Frame from the request
Length of the user data from the request
Ä 'Common status' on page 320: OK
User data from the request
Remaining user data are not relevant