Basics and mounting
Mounting periphery modules
Mounting periphery
modules
20
1.
Mount the mounting rail! Please consider that a clearance from the middle of the
mounting rail of at least 80mm above and 60mm below, respectively 80mm by
deployment of shield bus carriers, exist.
2.
Mount your head module such as CPU or field bus coupler.
3.
Before mounting the periphery modules you have to remove the bus cover at the
right side of the Head module by pulling it forward. Keep the cover for later
mounting.
4.
For mounting turn the locking lever of the module upward until it engages.
5.
For mounting place the module to the module installed before and push the module
to the mounting rail guided by the strips at the upper and lower side of the module.
6.
Turn the locking lever of the periphery module downward, again.