VIPA System SLIO
MEAS Measurement
method
FILT Filter selection
DFCT Dynamic Filter
Change Time
Dynamic filter delta
RO Rated output
HB300 | SM-AIO | | en | 17-05
n
During self-calibration, the CAL LED is on an the measured value is frozen.
n
00h de-activates the calibration.
Byte
Bit 7 ... 0
0
Measurement method
n
23h: 6 wire measurement
25h: 4 wire measurement
FFh: de-activated
n
Here you can choose between 4 and 6 wire measurement respectively disable the
measurement.
Byte
Bit 7 ... 0
0
Filter selection
n
00h: Filter de-activated
01h: Activate dynamic IIR filter
02h: IIR1
03h: IIR2
04h: IIR3
05h: IIR4
06h: IIR5
07h: IIR6
08h: IIR7
09h: IIR8
0Ah: FIR 50Hz
0Bh: FIR 60Hz
Filter functions
n
FIR 50/60 Hz
Suppression of mains frequency interference
n
Dynamic IIR filter
automatic selection
Filter selection dependent on the current weight change
n
Static IIR filter
De-activation respectively fix setting of a filter level (IIR1...IIR8)
Byte
Bit 7 ... 0
0...1
Sampling rate for filter change-over in ms
n
Here you can specify the time for re-evaluation for the filter change-over in ms.
Byte
Bit 7 ... 0
0...1
Limit value for filter change-over
n
Here you can specify the limit value for the filter change-over.
Byte
Bit 7 ... 0
0...1
Rated output in 0.0001mV/V
031-1CA20 - AI 1x16(24)Bit Strain gauge (DMS) > Parameter data
Analog Input
183