032-1CB40 - AO 2x16Bit 0(4)...20mA > Diagnostic data
0 ... 20mA
Output range
Current
(funct. no.)
(I)
0 ... 20mA
23.52mA
Siemens
20mA
S7 format
10mA
(31h)
0mA
Not possible, is limited to 0mA.
0 ... 20mA
25.00mA
Siemens
20mA
S5 format
10mA
(41h)
0mA
Not possible, is limited to 0mA.
4 ... 20mA
Output range
Current
(funct. no.)
(I)
4 ... 20mA
22.81mA
Siemens
20mA
S7 format
12mA
(30h)
4mA
0mA
4 ... 20mA
24.00mA
Siemens
20mA
S5 format
12mA
(40h)
4mA
0mA
4.11.3

Diagnostic data

404
Decimal
(D)
32511
27648
13824
0
20480
16384
8192
0
Decimal
(D)
32511
27648
13824
0
-6912
20480
16384
8192
0
-4096
So this module does not support diagnostic interrupt functions, the diagnostics data serve
for information about this module. On error the corresponding channel LED of the module
is activated and the error is registered in the diagnostics data.
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Wire-break (if parameterized)
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
underrange
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
E500h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
F000h
underrange