Diagnostic Data - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
0 ... 10V
Output range
Voltage
(funct. no.)
(U)
0 ... 10V
11,76V
Siemens
10V
S7 format
5V
(10h)
0V
Not possible, is limited to 0V.
0 ... 10V
12,5V
Siemens
10V
S5 format
5V
(20h)
0V
Not possible, is limited to 0V.

4.4.3 Diagnostic data

Name
Bytes
ERR_A
1
MODTYP
1
ERR_C
1
ERR_D
1
CHTYP
1
NUMBIT
1
NUMCH
1
CHERR
1
CH0ERR
1
HB300 | SM-AIO | | en | 17-05
Decimal
(D)
32511
27648
13824
0
20480
16384
8192
0
So this module does not support diagnostic interrupt functions, the diagnostics data serve
for information about this module. On error the corresponding channel LED of the module
is activated and the error is registered in the diagnostics data.
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Short-circuit/overload (if parameterized)
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
Function
Diagnostic
Module information
reserved
Diagnostic
Channel type
Number diagnostic bits per channel 08h
Number of channels of a module
Channel error
Channel-specific error channel 0
032-1BB30 - AO 2x12Bit 0...10V > Diagnostic data
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
underrange
Default
DS
00h
01h
15h
00h
00h
73h
02h
00h
00h
Analog Output
Formulas
IX
SX
2F01h
02h
03h
04h
05h
06h
07h
08h
09h
0Ah
345