VIPA System SLIO
Resistance
Measuring range
(funct. no.)
2 wire: PT100
(50h)
2 wire: PT1000
(51h)
2 wire: NI100
(52h)
2 wire: NI1000
(53h)
3 wire: PT100
(58h)
3 wire: PT1000
(59h)
3 wire: NI100
(5Ah)
3 wire: NI1000
(5Bh)
4 wire: PT100
(60h)
4 wire: PT1000
(61h)
4 wire: NI100
(62h)
4 wire: NI1000
HB300 | SM-AIO | | en | 17-05
Measuring value
+1000°C
-200 ... +850°C
-243°C
+1000°C
-200 ... +850°C
-243°C
+295°C
-60 ... +250°C
-105°C
+295°C
-60 ... +250°C
-105°C
+1000°C
-200 ... +850°C
-243°C
+1000°C
-200 ... +850°C
-243°C
+295°C
-60 ... +250°C
-105°C
+295°C
-60 ... +250°C
-105°C
+1000°C
-200 ... +850°C
-243°C
+1000°C
-200 ... +850°C
-243°C
+295°C
-60 ... +250°C
-105°C
+295°C
Measuring ranges and function numbers
Signal range
+10000
-2000 ... +8500
-2430
+10000
-2000 ... +8500
-2430
+2950
-600 ... +2500
-1050
+2950
-600 ... +2500
-1050
+10000
-2000 ... +8500
-2430
+10000
-2000 ... +8500
-2430
+2950
-600 ... +2500
-1050
+2950
-600 ... +2500
-1050
+10000
-2000 ... +8500
-2430
+10000
-2000 ... +8500
-2430
+2950
-600 ... +2500
-1050
+2950
Analog Input
Range
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
41