YASKAWA VIPA System SLIO Manual page 168

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1BF74 - AI 8x12Bit ±10V > Diagnostic data
Name
Bytes
ERR_A
1
MODTYP
1
ERR_C
1
ERR_D
1
CHTYP
1
NUMBIT
1
NUMCH
1
CHERR
1
CH0ERR
1
CH1ERR
1
CH2ERR
1
CH3ERR
1
CH4ERR
1
CH5ERR
1
CH6ERR
1
CH7ERR
1
DIAG_US
4
ERR_A Diagnostic
168
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Measuring range overflow
n
Measuring range underflow
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
Function
Diagnostic
Module information
reserved
Diagnostic
Channel type
Number diagnostic bits per channel
Number of channels of a module
Channel error
Channel-specific error channel 0
Channel-specific error channel 1
Channel-specific error channel 2
Channel-specific error channel 3
Channel-specific error channel 4
Channel-specific error channel 5
Channel-specific error channel 6
Channel-specific error channel 7
µs ticker
Byte
Bit 7 ... 0
0
n
Bit 0: set at module failure
n
Bit 1: set at internal error
n
Bit 2: set at external error
Bit 3: set at channel error
n
n
Bit 4: set at external auxiliary supply missing
n
Bit 6 ... 5: reserved
n
Bit 7: set at error in parameterization
Default
DS
00h
01h
15h
00h
00h
71h
08h
08h
00h
00h
00h
00h
00h
00h
00h
00h
00h
00h
HB300 | SM-AIO | | en | 17-05
VIPA System SLIO
IX
SX
2F01h
02h
03h
04h
05h
06h
07h
08h
09h
0Ah
0Bh
0Ch
0Dh
0Eh
0Fh
10h
11h
13h

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio