YASKAWA VIPA System SLIO Manual page 33

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
Isolation of conductors
HB300 | SM-AIO | | en | 17-05
n
Proof the correct fixing of the lead isolation.
Data lines must be laid isolated.
Analog lines must be laid isolated. When transmitting signals with small ampli-
tudes the one sided laying of the isolation may be favourable.
Lay the line isolation extensively on an isolation/protected earth conductor rail
directly after the cabinet entry and fix the isolation with cable clamps.
Make sure that the isolation/protected earth conductor rail is connected impe-
dance-low with the cabinet.
Use metallic or metallised plug cases for isolated data lines.
n
In special use cases you should appoint special EMC actions.
Consider to wire all inductivities with erase links.
Please consider luminescent lamps can influence signal lines.
Create a homogeneous reference potential and ground all electrical operating sup-
n
plies when possible.
Please take care for the targeted employment of the grounding actions. The
grounding of the PLC serves for protection and functionality activity.
Connect installation parts and cabinets with your PLC in star topology with the
isolation/protected earth conductor system. So you avoid ground loops.
If there are potential differences between installation parts and cabinets, lay suffi-
ciently dimensioned potential compensation lines.
Electrical, magnetically and electromagnetic interference fields are weakened by means
of an isolation, one talks of absorption. Via the isolation rail, that is connected conductive
with the rack, interference currents are shunt via cable isolation to the ground. Here you
have to make sure, that the connection to the protected earth conductor is impedance-
low, because otherwise the interference currents may appear as interference cause.
When isolating cables you have to regard the following:
n
If possible, use only cables with isolation tangle.
n
The hiding power of the isolation should be higher than 80%.
Normally you should always lay the isolation of cables on both sides. Only by means
n
of the both-sided connection of the isolation you achieve high quality interference
suppression in the higher frequency area. Only as exception you may also lay the iso-
lation one-sided. Then you only achieve the absorption of the lower frequencies. A
one-sided isolation connection may be convenient, if:
the conduction of a potential compensating line is not possible.
analog signals (some mV respectively µA) are transferred.
foil isolations (static isolations) are used.
With data lines always use metallic or metallised plugs for serial couplings. Fix the
n
isolation of the data line at the plug rack. Do not lay the isolation on the PIN 1 of the
plug bar!
n
At stationary operation it is convenient to strip the insulated cable interruption free
and lay it on the isolation/protected earth conductor line.
n
To fix the isolation tangles use cable clamps out of metal. The clamps must clasp the
isolation extensively and have well contact.
n
Lay the isolation on an isolation rail directly after the entry of the cable in the cabinet.
Lead the isolation further on to your PLC and don't lay it on there again!
CAUTION!
Please regard at installation!
At potential differences between the grounding points, there may be a
compensation current via the isolation connected at both sides.
Remedy: Potential compensation line
Basics and mounting
Installation guidelines
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio

Table of Contents