YASKAWA VIPA System SLIO Manual page 101

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
LIMIT_EN Limit value
monitoring
TEMPCNF Temperature
system
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
Voltage
-80 ... 80mV
Meas. range
(funct. no.)
-80 ... 80mV
Siemens S7 format
(11h)
-80 ... 80mV
Siemens S7 format
(21h)
HB300 | SM-AIO | | en | 17-05
Byte
Bit 7 ... 0
0
n
Bit 0: Limit value monitoring channel 0 (1: on)
n
Bit 1: Limit value monitoring channel 1 (1: on)
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
n
Bit 0, 1: Temperature system
Bit 7 ... 2: reserved
n
Byte
Bit 7 ... 0
0
n
Bit 0, 1: Interference frequency suppression
n
Bit 7 ... 2: reserved
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module.
With FFh the corresponding channel is deactivated.
Voltage
Decimal
(U)
(D)
94.07mV
32511
80mV
27648
0V
0
-80mV
-27648
-94.07mV
-32512
100mV
20480
80mV
16384
0V
0
-80mV
-16384
-100mV
-20480
00: °C
01: °F
10: K
01: 60Hz
10: 50Hz
Hex
7EFFh
6C00h
0000h
9400h
8100h
5000h
4000h
0000h
C000h
B000h
031-1BB90 - AI 2x16Bit TC > Parameter data
Range
Formulas
overrange
nominal range
underrange
overrange
nominal range
underrange
Analog Input
101