Analog Output
032-1BD30 - AO 4x12Bit 0...10V > Technical data

4.7.1 Technical data

Order no.
Type
Module ID
Current consumption/power loss
Current consumption from backplane bus
Power loss
Technical data analog outputs
Number of outputs
Cable length, shielded
Rated load voltage
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)
Voltage output short-circuit protection
Voltage outputs
Min. load resistance (voltage range)
Max. capacitive load (current range)
Max. inductive load (current range)
Output voltage ranges
Operational limit of voltage ranges
Basic error limit voltage ranges
Destruction limit against external applied voltage
Current outputs
Max. in load resistance (current range)
Max. inductive load (current range)
Typ. open circuit voltage current output
Output current ranges
Operational limit of current ranges
Basic error limit current ranges
Destruction limit against external applied voltage
Settling time for ohmic load
Settling time for capacitive load
Settling time for inductive load
Resolution in bit
Conversion time
Substitute value can be applied
Output data size
368
032-1BD30
SM 032
0503 25E0
90 mA
1.2 W
4
200 m
DC 24 V
ü
-
ü
ü
5 kΩ
1 µF
10 mA
0 V ... +10 V
+/-0.3%
+/-0.2%
max. 24V
-
-
-
-
-
-
-
-
1.5 ms
2 ms
-
12
2 ms all channels
no
8 Byte