YASKAWA VIPA System SLIO Manual page 323

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
3.27.7.2.3
Set Frame
Overview
Request
Byte
Value
B0
0x30
B1
?
B2
0x0?
B3
0x00
D00
?
...
D11
Response
Byte
Value
B0
0x30
B1
...
B2
...
B3
...
D00
...
...
D11
HB300 | SM-AIO | | en | 17-05
In the module you can combine some measurands to one data package (Frame), which
is transferred in one step
Description
n
Bit 3 ... 0: Error code (not relevant)
n
Bit 6 ... 4: 011 Telegram type 'Set Frame'
n
Bit 7: 0 fix reserved
Ä 'FR-ID' on page 310 of the Frame to be set
n
n
Length user data: 1 byte each measurand
DS-ID here fix 0
n
n
Common status (not relevant)
n
1 byte each measurand regarding that the measured values do not exceed the total
length of 12 byte. Here, the format of the measured values is taken into account.
Ä Chapter 3.27.6 'Measurands' on page 316
Ä 'Data type' on page 310
Description
n
Bit 3 ... 0:
Ä 'Status communication' on page 319
n
Bit 6 ... 4: 011 Telegram type 'Set Frame'
Bit 7: 0 fix reserved
n
n
FR-ID of the Frame from the request
n
Length of the user data from the request
n
DS-ID here fix 0
n
Ä 'Common status' on page 320
n
User data from the request
031-1PA00 - AI1x 3Ph 230/400V 1A > Process data communication
Ä 'Frame' on page 310. With 'Set Frame' a Frame can be built.
Analog Input
323