YASKAWA VIPA System SLIO Manual page 176

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1CA20 - AI 1x16(24)Bit Strain gauge (DMS) > In-/Output area
Input area
DMS_VAL measured value (weight value)
Bit number
31
30
Significance
SG
2
31Bit+SG
SG
Bit number
15
14
Significance
15
2
2
31Bit+SG
DMS_STAT Status
Addr.
Name
+3
DMS_STAT
*) These status bits are set by internal event of the module.
176
Addr.
Name
+0
DMS_VAL
+3
DMS_STAT
Byte 0
29
28
27
30
29
28
27
2
2
2
Byte 2
13
12
11
14
13
12
11
2
2
2
Bytes
Function
1
n
Status byte
n
Input Freeze
In the activated state no measurement values are passed to the digital filter.
As long as the command bit is set, this bit remains set.
Steady State
n
As soon as a measured value is longer than the time SSW within the tolerance
window SST, in the status word the Steady State bit is set.
As soon as this condition is not true, the last measured value is first used, the
comparison timer restarted and the bit is reset.
The values SSW and SST can be specified by the parametrization.
3.16.5 'Parameter data' on page 181
n
Self calibration
As long as the self calibration is active, this bit is set.
During the self calibration there are two reference values internally measured and
based on this the internal offset & factor are calculated.
With the self calibration the internal offset and gain error may be compensated.
The calibration interval CI can be preset by the parametrization.
Bytes
4
1
26
25
24
23
26
25
24
23
2
2
2
2
Measured value ...
10
9
8
7
10
9
8
7
2
2
2
2
... Measured value
Bit 0: 1 = Input Freeze active
Bit 1: 1 = Steady State active *
Bit 2: 1 = Self-calibration is running *
Bit 3: 1 = Tara was changed
Bit 4: 1 = Error in adjustment
Bit 5: 1 = Adjustment was changed
Bit 6: reserved
Bit 7: 1 = Zero balance respectively reference point set
Function
IX
Measured value
5470h/s
Status
5471h/s
Byte 1
22
21
20
19
22
21
20
19
2
2
2
2
Byte 3
6
5
4
3
6
5
4
3
2
2
2
2
HB300 | SM-AIO | | en | 17-05
VIPA System SLIO
SX
01h
02h
18
17
16
18
17
16
2
2
2
2
1
0
2
1
0
2
2
2
Ä Chapter

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: