Parameter Data - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
3.23.2

Parameter data

Name
Bytes
SUPR
1
CH0FN
1
CH1FN
1
CH2FN
1
CH3FN
1
SUPR Interference fre-
quency suppression
CHxFN Function number
channel x
HB300 | SM-AIO | | en | 17-05
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Function
Interference frequency suppression
Function number channel 0
Function number channel 1
Function number channel 2
Function number channel 3
Byte
Bit 7 ... 0
0
n
Bit 1, 0: Interference frequency suppression channel 0
n
Bit 3, 2: Interference frequency suppression channel 1
n
Bit 5, 4: Interference frequency suppression channel 2
n
Bit 7, 6: Interference frequency suppression channel 3
e.g.: 10101010: all channels frequency suppression 50Hz
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
031-1CD45 - AI 4x16Bit 0(4)...20mA > Parameter data
Default
00h
31h
31h
31h
31h
00: deactivated
01: 60Hz
10: 50Hz
Analog Input
DS
IX
SX
01h
3100h
01h
80h
3101h
02h
81h
3102h
03h
82h
3103h
04h
83h
3104h
05h
261

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio

Table of Contents