YASKAWA VIPA System SLIO Manual page 326

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A > Process data communication
Example 'Read Frame'
Request
Byte
Value
B0
0x20
B1
0x01
B2
0x71
B3
0x00
D00
-
...
D11
Response
Byte
Value
B0
0x20
B1
0x01
B2
0x71
B3
0x00
D00
0x00
D01
0x07
D02
0xA1
D03
0x20
D04
0x5A
D05
0x13
D06
0x88
D07
-
...
D11
326
In the example the previously via 'Set Frame' defined FR-ID (0x01) is requested with the
following measurands:
n
ID: 03: Counter: Active energy L1 (consumer): 4byte
ID: 13: total cos j: 1byte
n
n
ID: 12: Frequency 2byte
Description
Telegram type 'Read Frame'
Ä 'FR-ID' on page 310 of the Frame to be read (FR-ID = 1)
Length of the user data is 7
Ä 'DS-ID' on page 309 of the measured value to be read (DS-ID = 1)
Common status (not relevant)
User data (not relevant)
Description
Telegram type 'Read value' from the request
FR-ID of the Frame from the request
Length of the Frame with measured values: 7
DS-ID of the measured value from the request
Ä 'Common status' on page 320: OK
Counter: Active energy L1 (consumer): 500kWh
Total cos j: 0.9
Frequency: 50Hz
Remaining user data are not relevant