YASKAWA VIPA System SLIO Manual page 66

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1BB30 - AI 2x12Bit 0...10V > Diagnostic data
CHTYP Channel type
NUMBIT Diagnostic bits
NUMCH Channels
CHERR Channel error
CH0ERR / CH1ERR
Channel-specific
CH2ERR ... CH7ERR
reserved
DIAG_US µs ticker
66
Byte
Bit 7 ... 0
0
n
Bit 6 ... 0: Channel type
70h: Digital input
71h: Analog input
72h: Digital output
73h: Analog output
74h: Analog input/-output
76h: Counter
Bit 7: reserved
n
Byte
Bit 7 ... 0
0
Number of diagnostic bits per channel (here 08h)
Byte
Bit 7 ... 0
0
Number of channels of a module (here 02h)
Byte
Bit 7 ... 0
0
n
Bit 0: set at error in channel group 0
n
Bit 1: set at error in channel group 1
n
Bit 7 ... 2: reserved
Byte
Bit 7 ... 0
0
Channel-specific error channel x:
n
Bit 0: set at configuring/parameter assignment error
n
Bit 5 ... 1: reserved
n
Bit 6: set at measuring range underflow
n
Bit 7: set at measuring range overflow
Byte
Bit 7 ... 0
0
reserved
Byte
Bit 7 ... 0
0...3
Value of the µs ticker at the moment of the diagnostic
µs ticker
In the SLIO module there is a timer (µs ticker). With PowerON the timer starts counting
32
with 0. After 2
-1µs the timer starts with 0 again.
VIPA System SLIO
HB300 | SM-AIO | | en | 17-05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hb300Sm-aio

Table of Contents