Diagnostic Data - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
0(4) ... 20mA
Meas. range
Current
(funct. no.)
(I)
0 ... 20mA
23.52mA
Siemens
20mA
S7 format
10mA
(31h)
0mA
-3.52mA
0 ... 20mA
25.00mA
Siemens
20mA
S5 format
10mA
(41h)
0mA
-4,00mA
4 ... 20mA
22.81mA
Siemens
20mA
S7 format
12mA
(30h)
4mA
1.19mA
4 ... 20mA
24.00mA
Siemens
20mA
S5 format
12mA
(40h)
4mA
0.8mA
3.11.3

Diagnostic data

HB300 | SM-AIO | | en | 17-05
Decimal
(D)
32511
27648
13824
0
-4864
20480
16384
8192
0
-3277
32511
27648
13824
0
-4864
20480
16384
8192
0
-3277
So this module does not support diagnostic interrupt functions, the diagnostics data serve
for information about this module. On error the corresponding channel LED of the module
is activated and the error is registered in the diagnostics data.
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Measuring range overflow
n
Measuring range underflow
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
031-1BD40 - AI 4x12Bit 0(4)...20mA > Diagnostic data
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
ED00h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
F333h
underrange
7EFFh
overrange
6C00h
nominal range
3600h
0000h
ED00h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
F333h
underrange
Analog Input
Formulas
123