VIPA System SLIO
±10V
Meas. range
(funct. no.)
±10V
Siemens S7 format
(12h)
±10V
Siemens S5 format
(22h)
HB300 | SM-AIO | | en | 17-05
Voltage
Decimal
(U)
(D)
11.76V
32511
10V
27648
5V
13824
0V
0
-5V
-13824
-10V
-27648
-11.76V
-32512
12.5V
20480
10V
16384
5V
8192
0V
0
-5V
-8192
-10V
-16384
-12.5V
-20480
Measuring ranges and function numbers
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
CA00h
9400h
8100h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
E000h
C000h
B000h
underrange
Analog Input
Formulas