Parameter Data - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Output
032-1BD40 - AO 4x12Bit 0(4)...20mA > Parameter data
Order no.
Operating temperature
Storage temperature
Certifications
UL certification
KC certification

4.8.2 Parameter data

Name
Bytes
RES0
1
WIBRK_EN
1
CH0FN
1
CH1FN
1
CH2FN
1
CH3FN
1
WIBRK_EN Wire-break
recognition
CHxFN Function number
channel x
378
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Function
reserved
Wire-break recognition
Function number channel 0
Function number channel 1
Function number channel 2
Function number channel 3
Byte
Bit 7 ... 0
0
n
Bit 0: Wire-break recognition channel 0 (1: on)
n
Bit 1: Wire-break recognition channel 1 (1: on)
n
Bit 2: Wire-break recognition channel 2 (1: on)
n
Bit 3: Wire-break recognition channel 3 (1: on)
n
Bit 7 ... 4: reserved
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
032-1BD40
0 °C to 60 °C
-25 °C to 70 °C
yes
yes
Default
DS
00h
00h
00h
00h
31h
80h
31h
81h
31h
82h
31h
83h
VIPA System SLIO
IX
SX
3100h
01h
3101h
02h
3102h
03h
3103h
04h
3104h
05h
3105h
06h
HB300 | SM-AIO | | en | 17-05