Analog Input
Measuring ranges and function numbers
Measuring range
(funct. no.)
3 wire: 0 ... 3000W
(DAh)
4 wire: 0 ... 60W
(E0h)
4 wire: 0 ... 600W
(E1h)
4 wire: 0 ... 3000W
(E2h)
Temperature
Measuring range
(funct. no.)
Type J:
[Fe-Cu-Ni IEC]
-210 ... +1200°C
-346 ... 2192°F
63.2 ... 1473.2K
(B0h: ext. comp. 0°C)
(C0h: int. comp. 0°C)
Type K:
[Ni-Cr-Ni]
-270 ... +1372°C
-454 ... 2501.6°F
0 ... 1645.2K
(B1h: ext. comp. 0°C)
(C1h: int. comp. 0°C)
Type N:
[Ni-Cr-Si]
-270 ... +1300°C
-454 ... 2372°F
44
Measuring value
---
3528W
0 ... 3000W
---
70.55W
0 ... 60W
---
705.5W
0 ... 600W
---
3528W
0 ... 3000W
---
Measuring value
Measuring value in
in °C
°F
(0.1°C/digit)
(0.1°F/digit)
+14500
26420
-2100 ... +12000
-3460 ... 21920
---
---
+16220
29516
-2700 ... +13720
-4540 ... 25016
---
---
+15500
28220
-2700 ... +13000
-4540 ... 23720
Signal range
---
32511
0 ... 27648
---
32511
0 ... 27648
---
32511
0 ... 27648
---
32511
0 ... 27648
---
Measuring value in K
(0.1K/digit)
17232
632 ... 14732
---
18952
0 ... 16452
---
18232
0 ... 15732
VIPA System SLIO
Range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
underrange
Range
overrange
nominal range
underrange
overrange
nominal range
underrange
overrange
nominal range
HB300 | SM-AIO | | en | 17-05