VIPA System SLIO
Status indication
HB300 | SM-AIO | | en | 17-05
RUN
MF
green
red
●
○
●
●
○
●
○
○
X
B
red
>U
red
<U
red
>I
red
<cos
red
TEMP
green
P
on: ● | off: ○ | blinking: B | not relevant: X
Description
Bus communication is OK
Module status is OK
Bus communication is OK
Module status reports an error
Bus communication is not possible
Module status reports an error
Error at bus power supply
Ä Chapter 2.8 'Trouble shooting -
Error in configuration
LEDs' on page 31
○
Voltage in the parametrized range
●
Voltage limit value exceeded
○
Voltage in the parametrized range
Voltage limit value undershot
●
(omitted in 1-phase operation)
○
Current in the parametrized range
●
Current limit value exceeded
Phase shift cos j in the parametrized range
○
Phase shift cos j limit value undershot
●
(omitted in 1-phase operation)
○
Temperature in the parametrized range
●
Temperature limit value exceeded
P: Power-proportional
blinks with increasing frequency proportional to
B
the active power at 20 pulses/Wh. The current
transformer factor is not considered.
Analog Input
031-1PA00 - AI1x 3Ph 230/400V 1A
303