Advertisement

VIPA System SLIO
Pin assignment
Supplementation to the
installation guidelines
In-/Output area
HB300 | SM-AIO | | en | 17-05
For wires with a cross section of 0.08mm
Pos.
Function
1
+TC 0
2
-TC 0
3
---
4
---
5
+TC 1
6
-TC 1
7
---
8
---
I: Input
CAUTION!
Please consider that the electronic module AI 2x16Bit TC may exclusively
be used together with the terminal module 001-0AA20!
To avoid variations in temperature within the module, which may affect the accuracy of
the measurement, you should consider the following points when assembling:
n
Do not arrange the module directly apart from a power module with a high feeding
current.
Do not install the module at the end of a line.
n
The module should be in a static condition, i.e. the temperature should be as constant
n
as possible in the environment of your module (closed switchgear cabinet free from
air draught).
n
The accuracy is reached after approx. 30 minutes after entering the static condition.
At CPU, PROFIBUS and PROFINET the input respectively output area is embedded to
the corresponding address area.
2
up to 1.5mm
Type
Description
I
+ Channel 0
I
Ground Channel 0
---
not connected
---
not connected
I
+ Channel 1
I
Ground Channel 1
---
not connected
---
not connected
Analog Input
031-1BB90 - AI 2x16Bit TC
2
.
95