Diagnostic Data - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1BB30 - AI 2x12Bit 0...10V > Diagnostic data
Name
Bytes
CH0FN
1
CH1FN
1
CHxFN Function number
channel x
0 ... 10V
Meas. range
(funct. no.)
0 ... 10V
Siemens S7 format
(10h)
0 ... 10V
Siemens S5 format
(20h)

3.5.3 Diagnostic data

64
Function
Function number channel 0
Function number channel 1
In the following there are the measuring ranges with function number listed, which were
supported by the analog module. With FFh the corresponding channel is deactivated. The
formulas listed here allow you to transform an evaluated measuring value (digital value)
to a value assigned to the measuring range (analog value) and vice versa.
Voltage
Decimal
(U)
(D)
11.76V
32511
10V
27648
5V
13824
0V
0
-1.76V
-4864
12.5V
20480
10V
16384
5V
8192
0V
0
-2V
-3277
This module does not support diagnostic interrupt functions, the diagnostics data serve
for information about this module. On error the corresponding channel LED of the module
is activated and the error is registered in the diagnostics data.
The following errors are listed in the diagnostics data:
n
Error in project engineering / parameterization
n
Measuring range overflow
n
Measuring range underflow
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
Default
DS
10h
80h
10h
81h
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
ED00h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
F333h
underrange
VIPA System SLIO
IX
SX
3100h
01h
3101h
02h
Formulas
HB300 | SM-AIO | | en | 17-05