Parameter Data - YASKAWA VIPA System SLIO Manual

Analog signal modules - sm 03x
Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Analog Input
031-1BB40 - AI 2x12Bit 0(4)...20mA > Parameter data

3.6.2 Parameter data

Name
Bytes
CH0FN
1
CH1FN
1
CHxFN Function number
channel x
0(4) ... 20mA
Meas. range
Current
(funct. no.)
(I)
0 ... 20mA
23.52mA
Siemens
20mA
S7 format
10mA
(31h)
0mA
-3.52mA
0 ... 20mA
25.00mA
Siemens
20mA
S5 format
10mA
(41h)
0mA
-4,00mA
4 ... 20mA
22.81mA
Siemens
20mA
S7 format
12mA
(30h)
4mA
1.19mA
4 ... 20mA
24.00mA
Siemens
20mA
S5 format
12mA
(40h)
4mA
0.8mA
72
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Function
Function number channel 0
Function number channel 1
In the following there are the measuring ranges with corresponding function number
listed, which were supported by the analog module. With FFh the corresponding channel
is deactivated. The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog value) and vice
versa.
Decimal
(D)
32511
27648
13824
0
-4864
20480
16384
8192
0
-3277
32511
27648
13824
0
-4864
20480
16384
8192
0
-3277
Default
DS
31h
80h
31h
81h
Hex
Range
7EFFh
overrange
6C00h
nominal range
3600h
0000h
ED00h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
F333h
underrange
7EFFh
overrange
6C00h
nominal range
3600h
0000h
ED00h
underrange
5000h
overrange
4000h
nominal range
2000h
0000h
F333h
underrange
VIPA System SLIO
IX
SX
3100h
01h
3101h
02h
Formulas
HB300 | SM-AIO | | en | 17-05