Out Of Service Led On At Power-Up; Error Code During Operation - GE P24DM Technical Manual

Motor protection ied
Table of Contents

Advertisement

P24xM
Test
The IED resets when the power-up is complete. A record
4
error code is displayed.
3.4

OUT OF SERVICE LED ON AT POWER-UP

Test
Using the IED menu, confirm the Commission Test or Test
1
Mode setting is Enabled. If it is not Enabled, go to test 2.
Select the VIEW RECORDS column then view the last
2
maintenance record from the menu.
3.5

ERROR CODE DURING OPERATION

The IED performs continuous self-checking. If the IED detects an error it displays an error message, logs a
maintenance record and after a short delay resets itself. A permanent problem (for example due to a hardware
fault) is usually detected in the power-up sequence. In this case the IED displays an error code and halts. If the
problem was transient, the IED reboots correctly and continues operation. By examining the maintenance record
logged, the nature of the detected fault can be determined.
P24xM-TM-EN-2.1
Check
Check
Chapter 20 - Maintenance and Troubleshooting
Programmable scheme logic error due to excessive execution time. If
the IED powers up successfully, check the programmable logic for
feedback paths.
Other error codes relate to software errors on the main processor
board, contact the local service centre.
If the setting is Enabled, disable the test mode and make sure the Out of
Service LED is OFF.
Check for the H/W Verify Fail maintenance record. This indicates a
discrepancy between the IED model number and the hardware. Examine
the Maint Data; cell. This indicates the causes of the failure using bit
fields:
Bit Meaning
The application 'type' field in the Cortec does not match the
0
software ID
The 'subset' field in the model number does not match the
1
software ID
The 'platform' field in the model number does not match the
2
software ID
The 'product type' field in the model number does not
3
match the software ID
The 'protocol' field in the Cortec does not match the
4
software ID
The 'model' field in the Cortec does not match the software
5
ID
The first 'software version' field in the does not match the
6
software ID
The second 'software version' field in the Cortec does not
7
match the software ID
8
No VTs are fitted
9
No CTs are fitted
10
No Earth CT is fitted
11
No SEF CT is fitted
Action
Action