Autoreclose - GE L30 Instruction Manual

Ur series line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 AUTORECLOSE 1
5
5-212


AUTORECLOSE

AR1 FUNCTION:
Disabled
AR1 INITIATE:
MESSAGE
Off
AR1 BLOCK:
MESSAGE
Off
AR1 MAX NUMBER OF
MESSAGE
SHOTS: 1
AR1 REDUCE MAX TO 1:
MESSAGE
Off
AR1 REDUCE MAX TO 2:
MESSAGE
Off
AR1 REDUCE MAX TO 3:
MESSAGE
Off
AR1 MANUAL CLOSE:
MESSAGE
Off
AR1 MNL RST FRM LO:
MESSAGE
Off
AR1 RESET LOCKOUT IF
MESSAGE
BREAKER CLOSED: Off
AR1 RESET LOCKOUT ON
MESSAGE
MANUAL CLOSE: Off
AR1 BKR CLOSED:
MESSAGE
Off
AR1 BKR OPEN:
MESSAGE
Off
AR1 BLK TIME UPON
MESSAGE
MNL CLS: 10.000 s
AR1 DEAD TIME 1:
MESSAGE
1.000 s
AR1 DEAD TIME 2:
MESSAGE
2.000 s
AR1 DEAD TIME 3:
MESSAGE
3.000 s
AR1 DEAD TIME 4:
MESSAGE
4.000 s
AR1 ADD DELAY 1:
MESSAGE
Off
AR1 DELAY 1:
MESSAGE
0.000 s
AR1 ADD DELAY 2:
MESSAGE
Off
L30 Line Current Differential System
AUTORECLOSE 1(2)
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1, 2, 3, 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Off, On
Range: Off, On
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
5 SETTINGS
5.7.7 AUTORECLOSE
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents