Commissioning

Connect controller and Engineering PC

5.3
Connect controller and Engineering PC
A communication link from the engineering PC to the controller is required to commission the
controller with the »PLC Designer«. This communication link must be wired.
NOTICE
Unstable LAN connection due to the use of incorrect cable types.
The LAN connection may be interrupted.
▶ Exclusively use cables of the CAT5-S/FTP type or better.
▶ The unit is to be connected only to internal Ethernet networks without exiting a facility and
being subjected to TNVs.
In the "as delivered" condition, the IP address in the controller is preset to
192.168.5.99 so it can be commissioned quickly.
If you would like to change the IP address, you will find more information in chapter
name and IP configuration
^ 74
How to establish a physical connection between the controller and the engineering PC:
1. Plug the network cable into the engineering port X16 of the controller.
2. Use the network cable to connect the controller to the PC.
The controller is connected to the engineering PC.
A ping command can be issued from the console to test the availability of the controller using
the current IP address 192.168.5.99 or the newly configured address.
Additional information on configuring the network:
5.4

Set IP address on the PC

Recommended IP address for the engineering PC: 192.168.5.100
Standard IP address of the controller: 192.168.5.99
How to set the static IP address of the Engineering PC:
Preconditions
Direct connection between the engineering PC and the controller
1. Open the Network connections diagnostics window.
Control Panel\Network and Internet\Network Connections
2. Select the network interface which is connected to the controller.
3. Right-click on Properties.
4. Select Internet Protocol (TCP/IP).
5. Click on the Properties button.
6. Select the Alternate Configuration tab.
7. Select the User-defined option.
a) Enter the IP address of the engineering PC that matches the IP range of the controller.
b) Enter the subnet mask of the engineering PC.
8. Click OK to close the dialog box.
16
.