FC 300 Design Guide
NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control
keys [Hand on] [Auto on].
[Reset]
is used for resetting the frequency converter after an alarm (trip). It can be selected as Enable
[1] or Disable [0] via par. 0-43 Reset Keys on LCP.

Initialisation to Default Settings

Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par. 14-22)
1.
Select par. 14-22
2.
Press [OK]
3.
Select "Initialisation"
4.
Press [OK]
5.
Cut off the mains supply and wait until the
display turns off.
6.
Reconnect the mains supply - the fre-
quency converter is now reset.
Manual initialisation
1.
Disconnect from mains and wait until the
display turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the
same time while power up for LCP 102,
Graphical Display
2b.
Press [Menu] while power up for LCP 101,
Numerical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now program-
med according to default settings.
NB!
When you carry out manual initialisation, you also reset serial communication, RFI filter set-
tings (par. 14-50) and fault log settings.
120
How to Programme
Par. 14-22 initialises all except:
14-50
8-30
8-31
8-32
8-35
8-36
8-37
15-00 to 15-05
15-20 to 15-22
15-30 to 15-32
This parameter initialises all except:
15-00
15-03
15-04
15-05
MG.33.B7.02 - VLT is a registered Danfoss trademark
RFI 1
Protocol
Address
Baud Rate
Minimum Response Delay
Max Response Delay
Max Inter-char Delay
Operating data
Historic log
Fault log
Operating Hours
Power-up's
Over temp's
Over volt's