FC 300 Design Guide
[ Quick Menu ]
allows quick access to different Quick Menus such as:
-
My Personal Menu
-
Quick Set-up
-
Changes Made
-
Loggings
Use
[Quick Menu]
for programming the parameters belonging to the Quick Menu . It is possible to
switch directly between Quick Menu mode and Main Menu mode.
[Main Menu]
is used for programming all parameters.
It is possible to switch directly between Main Menu mode and Quick Menu mode.
Parameter shortcut can be carried out by pressing down the
rameter shortcut allows direct access to any parameter.
[Alarm Log]
displays an Alarm list of the five latest alarms (numbered A1-A5). To obtain additional
details about an alarm, use the arrow keys to manoeuvre to the alarm number and press [OK]. You will
now receive information about the condition of your frequency converter right before entering the alarm
mode.
[Back]
takes you to the previous step or layer in the navigation structure.
[Cancel]
annuls your last change or command as long as the display has not been changed.
[Info]
supplies information about a command,
parameter, or function in any display window. [In-
fo] provides detailed information whenever help is
needed.
Exit info mode by pressing either [Info], [Back],
or [Cancel].
Navigation Keys
The four navigation arrows are used to navigate between the different choices available in
Menu],
[Main Menu]
[OK]
is used for choosing a parameter marked by the cursor and for enabling the change of a parameter.
Local Control Key
for local control are found at
the bottom of the control panel.
[Hand On]
enables control of the frequency converter via the LCP. [Hand on] also starts the motor, and
it is now possible to enter the motor speed data by means of the arrow keys. The key can be selected as
Enable [1] or Disable [0] via par. 0-40 [Hand on] key on LCP.
External stop signals activated by means of control signals or a serial bus will override a "start" command
via the LCP.
The following control signals will still be active when [Hand on] is activated:
[Hand on] - [Off] - [Auto on]
Reset
Coasting stop inverse
Reversing
How to Programme
and
[Alarm
Log]. Use the keys to move the cursor.
MG.33.B7.02 - VLT is a registered Danfoss trademark
[Main Menu]
key for 3 seconds. The pa-
130BP046.10
[Quick
109