Danfoss FC 300 Design Manual page 149

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
2-20
Release Brake Current
Value:
0.00 - par. 16-37
Function:
Set the motor current for release of the mechan-
ical brake, when a start condition is present. The
upper limit is specified in par. 16-37 Inv. Max.
Current.
2-21
Activate Brake Speed [RPM]
Value:
0 - 60.000
Function:
Set the motor speed for activation of the mechan-
ical brake, when a stop condition is present. The
upper speed limit is specified in par. 4-53 Warning
Speed High.
2-22
Activate Brake Speed [Hz]
Value:
0 - 5000
Function:
Set the motor frequency for activation of the me-
chanical brake, when a stop condition is present.
2-23
Activate Brake Delay
Value:
0.0 - 5.0 s
Function:
Enter the brake delay time of the coast after
ramp-down time. The shaft is held at zero speed
with full holding torque. Ensure that the mechan-
ical brake has locked the load before the motor
enters coast mode. See Control of Mechanical
Brake section.
factory setting
How to Programme
0.00A
0RPM
0Hz
0.0s
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
value for use in communication via serial communication port
149